| General specifications | ||
|---|---|---|
| Switching function | Normally closed (NC) | |
| Output type | NAMUR | |
| Slot width | 3.5 mm | |
| Depth of immersion (lateral) | 5 ... 7 mm , typ. 6 mm | |
| Output type | 2-wire | |
| Nominal ratings | ||
| Nominal voltage | 8.2 V (Ri approx. 1 kΩ) | |
| Operating voltage | 5 ... 25 V | |
| Switching frequency | 0 ... 3000 Hz | |
| Hysteresis | 0.41 ... 0.6 mm | |
| Suitable for 2:1 technology | yes , Reverse polarity protection diode not required | |
| Current consumption | ||
| Measuring plate not detected | ≥ 3 mA at nominal voltage | |
| Measuring plate detected | ≤ 1 mA at nominal voltage | |
| Functional safety related parameters | ||
| MTTFd | 8415 a | |
| Mission Time (TM) | 20 a | |
| Diagnostic Coverage (DC) | 0 % | |
| Compliance with standards and directives | ||
| Standard conformity | ||
| NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 | |
| Standards | EN 60947-5-2:2007 EN 60947-5-2/A1:2012 IEC 60947-5-2:2007 IEC 60947-5-2 AMD 1:2012 | |
| Approvals and certificates | ||
| EAC conformity | TR CU 012/2011 | |
| FM approval | ||
| Control drawing | 116-0165 | |
| UL approval | cULus Listed, General Purpose | |
| CSA approval | cCSAus Listed, General Purpose | |
| CCC approval | CCC approval / marking not required for products rated ≤36 V | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 100 °C (-13 ... 212 °F) | |
| Mechanical specifications | ||
| Connection type | flexible leads LiY , 500 mm | |
| Core cross-section | 0.14 mm2 | |
| Housing material | PBT/PPS | |
| Degree of protection | IP67 | |
| Equipment protection level Ga | ||
| CE marking | [*PD-Z02585A*] | |
| ATEX marking | II 1G Ex ia IIC T6…T1 Ga The Ex-related marking can also be printed on the enclosed label. | |
| Standards | EN 60079-0:2012+A11:2013, EN 60079-11:2012 Ignition protection "Intrinsic safety" Use is restricted to the following stated conditions | |
| Appropriate type | SJ3,5-...-N... | |
| Effective internal capacitance | max. 50 nF ; a cable length of 10 m is considered. | |
| Effective internal inductance | max. 250 µH ; a cable length of 10 m is considered. | |
| Highest permissible ambient temperature | Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EU-type examination certificate. Note: Use the temperature table for category 1 !!! The 20 % reduction in accordance with EN 1127-1 has already been applied to the temperature table for category 1. | |
| Equipment protection level Gb | ||
| CE marking | [*PD-Z02585A*] | |
| ATEX marking | II 1G Ex ia IIC T6…T1 Ga The Ex-related marking can also be printed on the enclosed label. | |
| Standards | EN 60079-0:2012+A11:2013, EN 60079-11:2012 Ignition protection "Intrinsic safety" Use is restricted to the following stated conditions | |
| Appropriate type | SJ3,5-...-N... | |
| Effective internal capacitance | max. 50 nF ; a cable length of 10 m is considered. | |
| Effective internal inductance | max. 250 µH ; a cable length of 10 m is considered. | |
| Maximum permissible ambient temperature | Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EU-type examination certificate. | |
| Equipment protection level Da | ||
| CE marking | [*PD-Z02585A*] | |
| ATEX marking | II 1D Ex ia IIIC T135°C Da The Ex-related marking can also be printed on the enclosed label. | |
| Standards | EN 60079-0:2012+A11:2013, EN 60079-11:2012 Ignition protection "Intrinsic safety" Use is restricted to the following stated conditions | |
| Appropriate type | SJ3,5-...-N... | |
| Effective internal capacitance | max. 50 nF ; a cable length of 10 m is considered. | |
| Effective internal inductance | max. 250 µH ; a cable length of 10 m is considered. | |
| General information | ||
| Use in the hazardous area | see instruction manuals | |
| Category | 1G; 2G; 1D | |
| Instruction manuals | Dil | Dosya Tipi | Dosya Boyutu |
|---|---|---|---|
| Instruction manual | ENG | 45 KB | |
| Manuel d'instructions | FRA | 46 KB | |
| Betriebsanleitung | GER | 49 KB | |
| Manuale di istruzioni | ITA | 43 KB | |
| Manual de instrucciones | SPA | 45 KB |
| Instruction manuals | Dil | Dosya Tipi | Dosya Boyutu |
|---|---|---|---|
| Instruction manual | ENG | 45 KB | |
| Manuel d'instructions | FRA | 46 KB | |
| Betriebsanleitung | GER | 49 KB | |
| Manuale di istruzioni | ITA | 43 KB | |
| Manual de instrucciones | SPA | 45 KB |



II 1G Ex ia IIC T6…T1 Ga 