TEKLİF İSTE
CJ4-12GK-N-5M M12 Plastik Gövde, 4mm Algılama, Namur NO Çıkış, 5m Kablolu, Çıkıntılı Montaj, Kapasitif Sensör
0,00TL
KDV Hariç: 0,00TL
- Stok Yok: Var
- Marka: Pepperl Fuchs
- Ürün Kodu: CJ4-12GK-N-5M
İçerisinde Sipariş Verirseniz Yarın Kargo!
Ücretsiz Kargo
10.000TL Üzeri Kargo Bedava
Banka Havalesi
Banka havalesinde ekstra %4 indirim imkanı
Hızlı Teslimat
Maksimum 2 İş Günü İçinde Kargoya Verilir
Güvenli Alışveriş
256BİT SSL Sertifikası ile Koruma
General specifications | ||
---|---|---|
Switching function | Normally open (NO) | |
Output type | NAMUR | |
Rated operating distance | 4 mm | |
Installation | non-flush | |
Assured operating distance | 0 ... 2.88 mm | |
Output type | 2-wire | |
Nominal ratings | ||
Installation conditions | ||
A | 20 mm | |
B | 80 mm | |
C | 12 mm | |
F | 70 mm | |
Nominal voltage | 8 V | |
Operating voltage | 7 ... 12 V | |
Switching frequency | 0 ... 1 Hz | |
Current consumption | ||
Measuring plate not detected | max. 1 mA | |
Measuring plate detected | ≥ 2.4 mA | |
Functional safety related parameters | ||
MTTFd | 3299 a | |
Mission Time (TM) | 20 a | |
Diagnostic Coverage (DC) | 0 % | |
Compliance with standards and directives | ||
Standard conformity | ||
NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 | |
Standards | EN 60947-5-2:2007 IEC 60947-5-2:2007 | |
Approvals and certificates | ||
FM approval | ||
Control drawing | 116-0165 | |
UL approval | cULus Listed, General Purpose | |
CSA approval | cCSAus Listed, General Purpose | |
CCC approval | CCC approval / marking not required for products rated ≤36 V | |
Ambient conditions | ||
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Connection type | cable PVC , 5 m | |
Core cross-section | 0.34 mm2 | |
Housing material | PBT | |
Sensing face | PBT | |
Degree of protection | IP68 | |
Cable | ||
Bending radius | > 10 x cable diameter | |
Equipment protection level Ga | ||
CE marking | [*PD-Z02585A*] | |
ATEX marking | II 1G Ex ia IIC T6…T1 Ga The Ex-related marking can also be printed on the enclosed label. | |
Standards | EN 60079-0:2012+A11:2013, EN 60079-11:2012 Ignition protection "Intrinsic safety" Use is restricted to the following stated conditions | |
Appropriate type | CJ4-12GK-N... | |
Effective internal capacitance | max. 60 nF ; a cable length of 10 m is considered. | |
Effective internal inductance | negligibly small A cable length of 10 m is considered. | |
Highest permissible ambient temperature | Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EU-type examination certificate. Note: Use the temperature table for category 1 !!! The 20 % reduction in accordance with EN 1127-1 has already been applied to the temperature table for category 1. | |
Equipment protection level Gb | ||
CE marking | [*PD-Z02585A*] | |
ATEX marking | II 1G Ex ia IIC T6…T1 Ga The Ex-related marking can also be printed on the enclosed label. | |
Standards | EN 60079-0:2012+A11:2013, EN 60079-11:2012 Ignition protection "Intrinsic safety" Use is restricted to the following stated conditions | |
Appropriate type | CJ4-12GK-N... | |
Effective internal capacitance | max. 60 nF ; a cable length of 10 m is considered. | |
Effective internal inductance | negligibly small A cable length of 10 m is considered. | |
Maximum permissible ambient temperature | Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EU-type examination certificate. | |
Equipment protection level Da | ||
CE marking | [*PD-Z02585A*] | |
ATEX marking | II 1D Ex ia IIIC T135°C Da The Ex-related marking can also be printed on the enclosed label. | |
Standards | EN 60079-0:2012+A11:2013, EN 60079-11:2012 Ignition protection "Intrinsic safety" Use is restricted to the following stated conditions | |
Appropriate type | CJ4-12GK-N... | |
Effective internal capacitance | max. 60 nF ; a cable length of 10 m is considered. | |
Effective internal inductance | negligibly small A cable length of 10 m is considered. | |
General information | ||
Use in the hazardous area | see instruction manuals | |
Category | 1G; 2G; 1D |
Instruction manuals | Dil | Dosya Tipi | Dosya Boyutu |
---|---|---|---|
Instruction manual | ENG | 55 KB | |
Manuel d'instructions | FRA | 57 KB | |
Betriebsanleitung | GER | 58 KB | |
Manuale di istruzioni | ITA | 53 KB | |
Manual de instrucciones | SPA | 56 KB | |
Technical information | |||
Installation conditions | ENG | 219 KB | |
Einbaubedingungen | GER | 345 KB |
Instruction manuals | Dil | Dosya Tipi | Dosya Boyutu |
---|---|---|---|
Instruction manual | ENG | 55 KB | |
Manuel d'instructions | FRA | 57 KB | |
Betriebsanleitung | GER | 58 KB | |
Manuale di istruzioni | ITA | 53 KB | |
Manual de instrucciones | SPA | 56 KB | |
Technical information | |||
Installation conditions | ENG | 219 KB | |
Einbaubedingungen | GER | 345 KB |
Algılama | |
Mesafesi | 3 mm ... < 5 mm |
Bağlantı. | |
Prensibi | 2 Tel |
Çıkış | |
Fonksiyonu | (NO) |
Gövde | |
Materyali | Plastik |
Kontrol | |
Çıkış | Namur |
Montaj | |
Şekli | Kablolu |
Şaft | |
Gövde | M12 |
Voltaj | |
Girişi | DC |