TEKLİF İSTE
NJ1,5-6,5-N-5M Çap 6mm, namur, kablolu, 1,5mm algılama, endüktif sensör
0,00TL
KDV Hariç: 0,00TL
- Stok Yok: Var
- Marka: Pepperl Fuchs
- Ürün Kodu: NJ1,5-6,5-N-5M
İçerisinde Sipariş Verirseniz Bugün Kargo!
Ücretsiz Kargo
10.000TL Üzeri Kargo Bedava
Banka Havalesi
Banka havalesinde ekstra %4 indirim imkanı
Hızlı Teslimat
Maksimum 2 İş Günü İçinde Kargoya Verilir
Güvenli Alışveriş
256BİT SSL Sertifikası ile Koruma
General specifications | ||
---|---|---|
Switching function | Normally closed (NC) | |
Output type | NAMUR | |
Rated operating distance | 1.5 mm | |
Installation | flush | |
Assured operating distance | 0 ... 1.215 mm | |
Reduction factor rAl | 0.22 | |
Reduction factor rCu | 0.19 | |
Reduction factor r304 | 0.65 | |
Output type | 2-wire | |
Nominal ratings | ||
Nominal voltage | 8 V | |
Switching frequency | 0 ... 5000 Hz | |
Hysteresis | typ. % | |
Suitable for 2:1 technology | yes , Reverse polarity protection diode not required | |
Current consumption | ||
Measuring plate not detected | min. 3 mA | |
Measuring plate detected | ≤ 1 mA | |
Compliance with standards and directives | ||
Standard conformity | ||
NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 | |
Standards | EN 60947-5-2:2007 EN 60947-5-2/A1:2012 IEC 60947-5-2:2007 IEC 60947-5-2 AMD 1:2012 | |
Approvals and certificates | ||
EAC conformity | TR CU 012/2011 | |
UL approval | cULus Listed, General Purpose | |
CSA approval | cCSAus Listed, General Purpose | |
CCC approval | CCC approval / marking not required for products rated ≤36 V | |
Ambient conditions | ||
Ambient temperature | -25 ... 100 °C (-13 ... 212 °F) | |
Mechanical specifications | ||
Connection type | cable PVC , 5 m | |
Core cross-section | 0.14 mm2 | |
Housing material | Stainless steel 1.4305 / AISI 303 | |
Sensing face | PBT | |
Degree of protection | IP67 | |
Cable | ||
Bending radius | > 10 x cable diameter | |
Equipment protection level Ga | ||
CE marking | [*PD-Z02585A*] | |
ATEX marking | II 1G Ex ia IIC T6…T1 Ga The Ex-related marking can also be printed on the enclosed label. | |
Standards | EN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection "Intrinsic safety" Use is restricted to the following stated conditions | |
Appropriate type | NJ 1,5-6,5...-N... | |
Effective internal capacitance | max. 30 nF ; a cable length of 10 m is considered. | |
Effective internal inductance | max. 50 µH ; a cable length of 10 m is considered. | |
Ambient temperature | Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EC-type examination certificate. Note: Use the temperature table for category 1 !!! The 20 % reduction in accordance with EN 1127-1 has already been applied to the temperature table for category 1. | |
Equipment protection level Gb | ||
CE marking | [*PD-Z02585A*] | |
ATEX marking | II 1G Ex ia IIC T6…T1 Ga The Ex-related marking can also be printed on the enclosed label. | |
Standards | EN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection "Intrinsic safety" Use is restricted to the following stated conditions | |
Appropriate type | NJ 1,5-6,5...-N... | |
Effective internal capacitance | max. 30 nF ; a cable length of 10 m is considered. | |
Effective internal inductance | max. 50 µH ; a cable length of 10 m is considered. | |
Maximum permissible ambient temperature | Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EC-type examination certificate. | |
Equipment protection level Da | ||
CE marking | [*PD-Z02585A*] | |
ATEX marking | II 1D Ex ia IIIC T135°C Da The Ex-related marking can also be printed on the enclosed label. | |
Standards | EN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection "Intrinsic safety" Use is restricted to the following stated conditions | |
Appropriate type | NJ 1,5-6,5...-N... | |
Effective internal capacitance | max. 30 nF ; a cable length of 10 m is considered. | |
Effective internal inductance | max. 50 µH ; a cable length of 10 m is considered. | |
Maximum permissible ambient temperature | Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the surface temperature, and the effective internal reactance values can be found on the EC-type-examination certificate. The maximum permissible ambient temperature of the data sheet must be noted, in addition, the lower of the two values must be maintained. | |
General information | ||
Use in the hazardous area | see instruction manuals | |
Category | 1G; 2G; 1D |
Instruction manuals | Dil | Dosya Tipi | Dosya Boyutu |
---|---|---|---|
Instruction manual | ENG | 46 KB | |
Manuel d'instructions | FRA | 46 KB | |
Betriebsanleitung | GER | 49 KB | |
Manuale di istruzioni | ITA | 44 KB | |
Manual de instrucciones | SPA | 46 KB | |
Technical information | |||
Installation conditions | ENG | 191 KB | |
Einbaubedingungen | GER | 194 KB | |
warunki montażu | POL | 245 KB | |
Условия монтажа | RUS | 274 KB |
Instruction manuals | Dil | Dosya Tipi | Dosya Boyutu |
---|---|---|---|
Instruction manual | ENG | 46 KB | |
Manuel d'instructions | FRA | 46 KB | |
Betriebsanleitung | GER | 49 KB | |
Manuale di istruzioni | ITA | 44 KB | |
Manual de instrucciones | SPA | 46 KB | |
Technical information | |||
Installation conditions | ENG | 191 KB | |
Einbaubedingungen | GER | 194 KB | |
warunki montażu | POL | 245 KB | |
Условия монтажа | RUS | 274 KB |