General specifications | ||
---|---|---|
Switching function | Normally closed (NC) | |
Output type | NAMUR | |
Rated operating distance | 1.5 mm | |
Installation | flush | |
Assured operating distance | 0 ... 1.22 mm | |
Reduction factor rAl | 0 | |
Reduction factor rCu | 0 | |
Reduction factor r304 | 0.55 | |
Output type | 2-wire | |
Nominal ratings | ||
Nominal voltage | 8.2 V (Ri approx. 1 kΩ) | |
Switching frequency | 0 ... 400 Hz | |
Hysteresis | typ. % | |
Current consumption | ||
Measuring plate not detected | min. 3 mA | |
Measuring plate detected | ≤ 1 mA | |
Limit data | ||
Operating pressure | 350 bar (5076.4 psi) | |
Functional safety related parameters | ||
MTTFd | 10887 a | |
Mission Time (TM) | 20 a | |
Diagnostic Coverage (DC) | 0 % | |
Compliance with standards and directives | ||
Standard conformity | ||
NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 | |
Standards | EN 60947-5-2:2007 EN 60947-5-2/A1:2012 IEC 60947-5-2:2007 IEC 60947-5-2 AMD 1:2012 | |
Approvals and certificates | ||
EAC conformity | TR CU 012/2011 | |
UL approval | cULus Listed, General Purpose | |
CSA approval | cCSAus Listed, General Purpose | |
Ambient conditions | ||
Ambient temperature | -25 ... 85 °C (-13 ... 185 °F) | |
Mechanical specifications | ||
Connection type | Connector plug M12 x 1 , 4-pin | |
Housing material | Stainless steel 1.4305 / AISI 303 | |
Sensing face | Ceramic | |
Degree of protection | IP67 | |
Mass | 41.81 g | |
Equipment protection level Gb | ||
CE marking | [*PD-Z02585A*] | |
ATEX marking | II 2G Ex ia IIC T6…T1 Gb The Ex-related marking can also be printed on the enclosed label. | |
Standards | EN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection "Intrinsic safety" Use is restricted to the following stated conditions | |
Appropriate type | NJ1,5-18GM-N-D.. | |
Effective internal inductivity | max. 50 nF ; a cable length of 10 m is considered. | |
Effective internal inductance | max. 60 µH ; a cable length of 10 m is considered. | |
Maximum permissible ambient temperature | Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EC-type examination certificate. | |
Equipment protection level Da | ||
CE marking | [*PD-Z02585A*] | |
ATEX marking | II 1D Ex ia IIIC T135°C Da The Ex-related marking can also be printed on the enclosed label. | |
Standards | EN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection "Intrinsic safety" Use is restricted to the following stated conditions | |
Appropriate type | NJ1,5-18GM-N-D.. | |
Effective internal inductivity | max. 50 nF ; a cable length of 10 m is considered. | |
Effective internal inductance | max. 60 µH ; a cable length of 10 m is considered. | |
Maximum permissible ambient temperature | Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the surface temperature, and the effective internal reactance values can be found on the EC-type-examination certificate. The maximum permissible ambient temperature of the data sheet must be noted, in addition, the lower of the two values must be maintained. | |
General information | ||
Use in the hazardous area | see instruction manuals | |
Category | 2G; 1D |
Algılama | |
Mesafesi | < 3 mm |
Bağlantı. | |
Prensibi | 2 Tel |
Çıkış | |
Fonksiyonu | (NC) |
Kontrol | |
Çıkış | Namur |
Montaj | |
Şekli | M12 Soketli |
Özel | |
Uygulama | Yüksek Basınca Dayanıklı |
Şaft | |
Gövde | M18 |
Voltaj | |
Girişi | DC |